Proceedings of the 2nd International Conference On Systems Engineering and Modeling (ICSEM 2013)

Numerical Analysis on Parameters Adjustment of Smoke Control System in a Complicated Underground Commercial Zone

Authors
Dewen Li, Jingzhao Zhang
Corresponding Author
Dewen Li
Available Online April 2013.
DOI
10.2991/icsem.2013.155How to use a DOI?
Keywords
Parameter adjustment, Underground commercial zone, Smoke control system, Evacuation time
Abstract

The technical parameters adjustment of smoke control system in a complicated underground commercial zone is studied by numerical simulations. An underground fire model (it encloses a hotel, a supermarket, and a net bar) and five typical fire scenarios are designed. The Fire Dynamic Simulator code is used to investigate the characteristics of fire spread and smoke movement, and obtain the available safety egress times in different fire scenarios. The required safety egress time is calculated based on the data of actual simulation exercises and numerical simulation by Building EXODUS. The simulation results show that, when the smoke exhaust rate is 5.56 cubic meter per second and air low rate reaches 3.89 cubic meter per second simultaneously, the available safety egress time is more than the required safety egress time.

Copyright
© 2013, the Authors. Published by Atlantis Press.
Open Access
This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).

Download article (PDF)

Volume Title
Proceedings of the 2nd International Conference On Systems Engineering and Modeling (ICSEM 2013)
Series
Advances in Intelligent Systems Research
Publication Date
April 2013
ISBN
10.2991/icsem.2013.155
ISSN
1951-6851
DOI
10.2991/icsem.2013.155How to use a DOI?
Copyright
© 2013, the Authors. Published by Atlantis Press.
Open Access
This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).

Cite this article

TY  - CONF
AU  - Dewen Li
AU  - Jingzhao Zhang
PY  - 2013/04
DA  - 2013/04
TI  - Numerical Analysis on Parameters Adjustment of Smoke Control System in a Complicated Underground Commercial Zone
BT  - Proceedings of the 2nd International Conference On Systems Engineering and Modeling (ICSEM 2013)
PB  - Atlantis Press
SP  - 755
EP  - 759
SN  - 1951-6851
UR  - https://doi.org/10.2991/icsem.2013.155
DO  - 10.2991/icsem.2013.155
ID  - Li2013/04
ER  -