- Abstract
Influence of electrical joint compound on electrical contact overheating energy consumption is studied in this paper. The high current test were made under different current(400A 600A 800A and 1000A). Aluminum-aluminum connections are selected to conduct contact resistance test and temperature rise test. The results show that contact resistance is reduced about 50%, and the temperature of electrical connection decreased 20 . The results show that there is remarkable effect after applying the compound. Electrical joint compound can reduce overheating defects and increase the reliability of electrical connection.
- Copyright
- © 2015, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Guogang Wang AU - Yueju Zhao AU - Liusuo Wu AU - Zhigang Kong PY - 2015/10 DA - 2015/10 TI - Influence of Electrical Joint Compound on Electrical Contact Overheating of Overhead Line BT - Proceedings of the 2015 2nd International Workshop on Materials Engineering and Computer Sciences PB - Atlantis Press SP - 124 EP - 128 SN - 2352-538X UR - https://doi.org/10.2991/iwmecs-15.2015.24 DO - 10.2991/iwmecs-15.2015.24 ID - Wang2015/10 ER -