Study on Damage Probability of High Voltage Electrical Equipment under Different Seismic Intensity
- DOI
- 10.2991/aece-16.2017.140How to use a DOI?
- Keywords
- eismic intensity; substation; high voltage electrical equipment; damage probability; vulnerability curve
- Abstract
Damages of transformer, potential transformer, current transformer, circuit breaker, disconnecting switch, arrester and other kinds of high voltage electrical equipments in substation under different seismic intensities have been summarized based on the damage data of electrical power system during Wenchuan earthquake. Damage probability density function curve and damage probability curve (vulnerability curve) of above high voltage electrical equipments have been established based on seismic intensity through normal distribution function and its accumulated function. Results show that transformer is the most vulnerable equipment which can be damaged in low seismic intensity, next to which are circuit breaker, arrester, PT, CT, disconnecting switch; the damage probability curves of PT, CT and disconnecting switch are very similar.
- Copyright
- © 2017, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Rushan LIU AU - Mingpan XIONG AU - Rongxing SHU PY - 2016/12 DA - 2016/12 TI - Study on Damage Probability of High Voltage Electrical Equipment under Different Seismic Intensity BT - Proceedings of the 2016 International Conference on Architectural Engineering and Civil Engineering PB - Atlantis Press SP - 652 EP - 656 SN - 2352-5401 UR - https://doi.org/10.2991/aece-16.2017.140 DO - 10.2991/aece-16.2017.140 ID - LIU2016/12 ER -