Research on Effectiveness and Operational Monitoring after Adding Passivator in Transformers
Authors
Yihua Qian, Shufang Zeng, Yaohong Zhao, Shun’an Cao
Corresponding Author
Yihua Qian
Available Online September 2015.
- DOI
- 10.2991/ifeesm-15.2015.103How to use a DOI?
- Keywords
- Transformers, Corrosive sulfur, passivator, operational monitoring
- Abstract
After adding passivators in corrosive sulfur-containing transformers, conducted follow-up research and monitoring on the effectiveness and comsumption of passivator, and monitor the quality of transformer oil after adding passivator, which aims to provide a reference for the operational monitoring after adding passivator and is of great significance to the safe and stable operation of the power grid. The research has shown that the passivator can effectively protect the copper wire from corrosive sulfur, the oil quality and chromatographic trace results were normal, and transformers ran normally and stably.
- Copyright
- © 2015, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Yihua Qian AU - Shufang Zeng AU - Yaohong Zhao AU - Shun’an Cao PY - 2015/09 DA - 2015/09 TI - Research on Effectiveness and Operational Monitoring after Adding Passivator in Transformers BT - Proceedings of the 2015 International Forum on Energy, Environment Science and Materials PB - Atlantis Press SP - 544 EP - 549 SN - 2352-5401 UR - https://doi.org/10.2991/ifeesm-15.2015.103 DO - 10.2991/ifeesm-15.2015.103 ID - Qian2015/09 ER -