Proceedings of the 2015 3rd International Conference on Machinery, Materials and Information Technology Applications

Effects of Installation Methods on the Operating Environment of Outdoor Units on the Existing Platform

Authors
Jiawei Hu, Shunyu Su, Yuyun Li
Corresponding Author
Jiawei Hu
Available Online November 2015.
DOI
10.2991/icmmita-15.2015.214How to use a DOI?
Keywords
outdoor unit; operating environment; installation methods; coefficient of performance
Abstract

Using the method of air enthalpy difference, an experiment on the 3HP air conditioner was conducted by changing the installation conditions. And some relevant parameters of the test system were measured by computer. The results show that, in cooling conditions, the thermal environment of the outdoor unit deteriorated when both sides of the shutter were closed, which was not conducive to the operation of the unit. If it is inevitable, we should increase the distance between the inlet and the shutter, or incline the outdoor unit properly to make the unit operate better. Besides, with the increase of the inlet temperature, the downtrend of COP changed from fast to slow in cooling conditions. However, the installation places of outdoor unit had little effect on the COP in heating conditions.

Copyright
© 2015, the Authors. Published by Atlantis Press.
Open Access
This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).

Download article (PDF)

Volume Title
Proceedings of the 2015 3rd International Conference on Machinery, Materials and Information Technology Applications
Series
Advances in Computer Science Research
Publication Date
November 2015
ISBN
10.2991/icmmita-15.2015.214
ISSN
2352-538X
DOI
10.2991/icmmita-15.2015.214How to use a DOI?
Copyright
© 2015, the Authors. Published by Atlantis Press.
Open Access
This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).

Cite this article

TY  - CONF
AU  - Jiawei Hu
AU  - Shunyu Su
AU  - Yuyun Li
PY  - 2015/11
DA  - 2015/11
TI  - Effects of Installation Methods on the Operating Environment of Outdoor Units on the Existing Platform
BT  - Proceedings of the 2015 3rd International Conference on Machinery, Materials and Information Technology Applications
PB  - Atlantis Press
SP  - 1164
EP  - 1168
SN  - 2352-538X
UR  - https://doi.org/10.2991/icmmita-15.2015.214
DO  - 10.2991/icmmita-15.2015.214
ID  - Hu2015/11
ER  -