Analysis of Two Points Grounding Accident in CT Secondary Circuit
- DOI
- 10.2991/icmmct-18.2018.39How to use a DOI?
- Keywords
- Current transformer, Relay protection, Impedance
- Abstract
The current transformer (CT) is a kind of transformer. The working principle of CT is briefly introduced.Combined with the actual case of relay error trip accident, the specific cause of the accident caused by two point grounding of the secondary circuit loop of the current transformer is further analyzed. There are two points grounding in the B phase circuit in the current transformer. The disturbance of instantaneous potential difference between two points of the ground network causes the protection device to flow into the larger current, thus causing the differential protection device to act. At the same time, the standard requirements for the secondary circuit grounding of the current transformer are put forward. The preventive measures that can be taken in every link of substation operation and maintenance are given.
- Copyright
- © 2018, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Yuanyi Li AU - Yueyue Li AU - Qixin Nie AU - Qian Cheng AU - Hui Tang AU - Yuan Lin AU - Fusheng Zhang AU - Diancai Shi AU - Ren Liu AU - Chuanzong Zhao PY - 2018/06 DA - 2018/06 TI - Analysis of Two Points Grounding Accident in CT Secondary Circuit BT - Proceedings of the 2018 6th International Conference on Machinery, Materials and Computing Technology (ICMMCT 2018) PB - Atlantis Press SP - 198 EP - 201 SN - 2352-5401 UR - https://doi.org/10.2991/icmmct-18.2018.39 DO - 10.2991/icmmct-18.2018.39 ID - Li2018/06 ER -