Research on the Distribution Network’s Single-phase Short-circuit Faults with Wavelet Transform
- DOI
- 10.2991/isrme-15.2015.235How to use a DOI?
- Keywords
- Single-phase Short-circuit Faults; Wavelet Transform; Wavelet Energy; Transient Zero Sequence Current
- Abstract
According to the problem that the single phase grounding fault location is difficult to detect, a novel method of identifying fault line for single phase grounding fault is presented, based on the detailed analysis of the transient zero sequence network’s fault characteristics in the small current neutral grounding power system. Experiments show that this method is immune to many factors such as the initial fault current switch angle, fault distance, transition resistance, power arc, the power distribution system operation mode and so on. It not only can detect the single phase high impedance grounding fault accurately which occurs at the terminal of transmission line, it also can detect the fault which occurs when the phase voltage is near zero.
- Copyright
- © 2015, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Hongyuan Huang AU - Yan Xu PY - 2015/04 DA - 2015/04 TI - Research on the Distribution Network’s Single-phase Short-circuit Faults with Wavelet Transform BT - Proceedings of the 2015 International Conference on Intelligent Systems Research and Mechatronics Engineering PB - Atlantis Press SP - 1137 EP - 1142 SN - 1951-6851 UR - https://doi.org/10.2991/isrme-15.2015.235 DO - 10.2991/isrme-15.2015.235 ID - Huang2015/04 ER -