Proceedings of the 2015 2nd International Forum on Electrical Engineering and Automation (IFEEA 2015)

Measurement Analysis of Electromagnetic Disturbance of the Secondary Sides of TA&TV in Local Control Cubicle of Dead Tank and Live Tank SF6 Circuit-breaker

Authors
Qiang Xu, Jianfei Ji, Jiayu Huang
Corresponding Author
Qiang Xu
Available Online January 2016.
DOI
10.2991/ifeea-15.2016.30How to use a DOI?
Keywords
dead tank type, live tank type, electromagnetic disturbance, secondary circuit, circuit-breaker
Abstract

The secondary circuit in substations is in a strong electromagnetic environment, and intelligent devices may be affected by electromagnetic disturbance signals. Meanwhile, with the local installation of intelligent devices, the electromagnetic disturbance of its working environment may be further strengthened. In recent years, there have been many accidents about abnormal operation of intelligent devices caused by the disturbance of secondary circuit in substations by circuit breaker and isolation switch. Therefore, it is with great significance to study the electromagnetic compatibility issue of the secondary circuit in substations. This paper has tested and recorded the electromagnetic disturbance in TA&TV secondary side of the local cabinet in the 500kV substation caused by the dead tank and live tank type circuit-breaker. The time domain and frequency domain of the measurement results are analyzed, the result of which indicates that the amplitudes of electromagnetic transient signals caused by the dead tank type breaker operation are all greater than that caused by the live tank type of breaker operation. However, the frequency of disturbance signals caused by dead tank circuit breaker is mostly concentrated in the KHz level, but that caused by the live tank type of breaker is distributed in the high-frequency section of MHz. Finally, some suggestions are proposed to improve the electromagnetic compatibility performance of the on-site secondary smart devices.

Copyright
© 2016, the Authors. Published by Atlantis Press.
Open Access
This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).

Download article (PDF)

Volume Title
Proceedings of the 2015 2nd International Forum on Electrical Engineering and Automation (IFEEA 2015)
Series
Advances in Engineering Research
Publication Date
January 2016
ISBN
978-94-6252-153-7
ISSN
2352-5401
DOI
10.2991/ifeea-15.2016.30How to use a DOI?
Copyright
© 2016, the Authors. Published by Atlantis Press.
Open Access
This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).

Cite this article

TY  - CONF
AU  - Qiang Xu
AU  - Jianfei Ji
AU  - Jiayu Huang
PY  - 2016/01
DA  - 2016/01
TI  - Measurement Analysis of Electromagnetic Disturbance of the Secondary Sides of TA&TV in Local Control Cubicle of Dead Tank and Live Tank SF6 Circuit-breaker
BT  - Proceedings of the 2015 2nd International Forum on Electrical Engineering and Automation (IFEEA 2015)
PB  - Atlantis Press
SP  - 151
EP  - 157
SN  - 2352-5401
UR  - https://doi.org/10.2991/ifeea-15.2016.30
DO  - 10.2991/ifeea-15.2016.30
ID  - Xu2016/01
ER  -