Optimization of the surface electric field of transmission line fitting on 500kV line in high altitude area
- DOI
- 10.2991/icmmse-16.2016.45How to use a DOI?
- Keywords
- Hing Altitude, Fitting, Electric Field Optimization, Transmission Line
- Abstract
The corona discharge of EHV transmission lines in high altitude area is very serious. Based on the Jiantang-Yulong 500kV power transmission project, we using Ansys software to calculate the surface electric field of 500 kV double circuit AC transmission line insulator and fittings. We get the voltage distribution of upper and middle and lower phase insulator string and the surface electric field distribution of fitting. According to the method of standard recommend, we get the corona electric field of fittings in high altitude (4km) are and compared with the result of the calculation. Then, we gives the optimization scheme of equalizing ring is rotated by 90 DEG and diameter increased to 55mm. The results show that the optimization scheme can effectively reduce the maximum electric field strength of the pressure ring and below the corona electric field value of fittings in high altitude.
- Copyright
- © 2016, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Qin Li PY - 2016/03 DA - 2016/03 TI - Optimization of the surface electric field of transmission line fitting on 500kV line in high altitude area BT - Proceedings of the 2016 International Conference on Mechanics, Materials and Structural Engineering PB - Atlantis Press SP - 266 EP - 271 SN - 2352-5401 UR - https://doi.org/10.2991/icmmse-16.2016.45 DO - 10.2991/icmmse-16.2016.45 ID - Li2016/03 ER -