A critical comparison of energy efficiency evaluation for condensing units in Chinese National Standard and EU Regulation
- DOI
- 10.2991/iceat-16.2017.60How to use a DOI?
- Keywords
- Condensing unit, Chinese National Standard, EU Eco-design Regulation, COP, SEPR,Energy efficiency evaluation
- Abstract
For the energy efficiency evaluation of condensing units, the European (EU) Eco-design Regulation No 2015/1095 sets ecological standards, and Chinese National Standard GB/T 21363-2008 makes requirements on the performance of the units. In this paper, a critical comparison of the energy efficiency evaluation of condensing units for medium temperature application set in No 2015/1095 and GB 21363-2008 is made and illustrated by a time table of the Copeland Condensing Units to be admitted to Chinese and European market. With a typical condensing unit as the sample, charts are developed and the numerical relationship of coefficient of performance (COP) and Season Energy Performance Ratio (SEPR) is calculated to find the disparity between No 2015/1095 and GB/T 21363-2008. It is concluded that GB/T 21363-2008 requires the COP threshold values too much higher than No 2015/1095 does but considers little ecological environmental protection.
- Copyright
- © 2017, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Y. HUANG AU - Y.Y. JIANG AU - J.Y. ZHANG AU - Z.B. ZHANG PY - 2016/05 DA - 2016/05 TI - A critical comparison of energy efficiency evaluation for condensing units in Chinese National Standard and EU Regulation BT - Proceedings of the 2016 International Conference on Engineering and Advanced Technology PB - Atlantis Press SP - 292 EP - 299 SN - 2352-5401 UR - https://doi.org/10.2991/iceat-16.2017.60 DO - 10.2991/iceat-16.2017.60 ID - HUANG2016/05 ER -