A Novel three-phase unbalance Control Strategy of SST under Passive Microgrid
- DOI
- 10.2991/iccsee.2013.419How to use a DOI?
- Keywords
- Three-phase umbalance control strategy, solid state transformer, passive microgrid, negative-sequence current calculation module
- Abstract
Three-phase unbalance control strategy is used to improve the system performance when three-phase unbalance load or fault happens. However, when the distributed generation selected as the master in the microgrid stop working, due to the loss of system voltage direction, the traditional control strategy is no longer applicable. In order to maintain the stable operation of the SST (Solid State Transformer) under passive microgrid model when three-phase unbalances occur in the microgrid, the paper came up a novel balance control strategy under passive microgrid model. The control strategy is based on the voltage and current double-loop control strategy, and uses a negative sequence current module to calculation the negative sequence reference current, prevent three-phase unbalance from entering into distribution grid side and improve the control performance of the SST. The simulation results have proved the validity and efficiency of the three-phase unbalance control strategy.
- Copyright
- © 2013, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Renjie Ding AU - Caiqi Zhou AU - Yuwei Zhao PY - 2013/03 DA - 2013/03 TI - A Novel three-phase unbalance Control Strategy of SST under Passive Microgrid BT - Proceedings of the 2nd International Conference on Computer Science and Electronics Engineering (ICCSEE 2013) PB - Atlantis Press SP - 1674 EP - 1677 SN - 1951-6851 UR - https://doi.org/10.2991/iccsee.2013.419 DO - 10.2991/iccsee.2013.419 ID - Ding2013/03 ER -