Proceedings of the 2015 5th International Conference on Computer Sciences and Automation Engineering

Simulation Analysis of Ferromagnetic Resonance of Low Magnetic Flux Density-Type PT under Single-Phase Earth Fault of 10kV Power Grid

Authors
Lin Gong, Xiaorui Hu, Haibo Wang, Xiaoyong Zhang, Fei Xiang, Jinyu Wang, Bin Wang
Corresponding Author
Lin Gong
Available Online February 2016.
DOI
10.2991/iccsae-15.2016.100How to use a DOI?
Keywords
Low Magnetic Flux Density-Type Potential Transformer; Ferromagnetic Resonance; Single-Phase Grounding; Potential Transformer Parallel; Simulink.
Abstract

In a neutral nongrounding power system, the excitation impedance of an electromagnetic potential transformer (PT) and a ground capacitance power transmission line of an electric power system can form a resonant circuit that causes ferroresonance and endangers the security and stability of the power system. This study analyzes a theory of ferromagnetic resonance that occurs under a single-phase earth fault in the power system of a PT, and Simulink is used to establish a simulation model of PT ferromagnetic resonance. Through this model, Simulink conducts an analysis of the ferromagnetic resonance simulation for the isolated operation of an ordinary PT and a low magnetic flux density-type PT, the parallel operation of these two PTs, and the parallel operation of two low magnetic flux density-type PTs. Simulation results show that ferromagnetic resonance phenomenon does not occur easily in a PT with good excitation characteristics. However, ferromagnetic resonance can be generated easily in PT parallel connections.

Copyright
© 2016, the Authors. Published by Atlantis Press.
Open Access
This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).

Download article (PDF)

Volume Title
Proceedings of the 2015 5th International Conference on Computer Sciences and Automation Engineering
Series
Advances in Computer Science Research
Publication Date
February 2016
ISBN
10.2991/iccsae-15.2016.100
ISSN
2352-538X
DOI
10.2991/iccsae-15.2016.100How to use a DOI?
Copyright
© 2016, the Authors. Published by Atlantis Press.
Open Access
This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).

Cite this article

TY  - CONF
AU  - Lin Gong
AU  - Xiaorui Hu
AU  - Haibo Wang
AU  - Xiaoyong Zhang
AU  - Fei Xiang
AU  - Jinyu Wang
AU  - Bin Wang
PY  - 2016/02
DA  - 2016/02
TI  - Simulation Analysis of Ferromagnetic Resonance of Low Magnetic Flux Density-Type PT under Single-Phase Earth Fault of 10kV Power Grid
BT  - Proceedings of the 2015 5th International Conference on Computer Sciences and Automation Engineering
PB  - Atlantis Press
SP  - 540
EP  - 547
SN  - 2352-538X
UR  - https://doi.org/10.2991/iccsae-15.2016.100
DO  - 10.2991/iccsae-15.2016.100
ID  - Gong2016/02
ER  -