Numerical Simulation on Heat Pipe Heat Exchanger: Effects of Different Wind Speeds
- DOI
- 10.2991/iccmcee-15.2015.51How to use a DOI?
- Keywords
- Heat pipe; Ventilation; Numerical simulation; Heat exchanger
- Abstract
The heat pipe heat exchanger is applied widely with the advantages of low investment, small volume and good effect of heat transfer. To make a full and reasonable use of the heat resource, a heat pipe heat exchanger is introduced in this paper. Numerical simulation of the heat pipe heat exchanger with different wind speeds is carried out by the CFD software FLUENT. The temperature, velocity contours and effects of heat transfer were compared in different wind speed conditions such as 0.02m/s, 0.04m/s, 0.06m/s,0.08mm/s, 0.1m/s and 0.12m/s. The maximum difference of cold and hot air heat flow rate is 5.344W in the air velocity of 0.04m/s. And the results show that rate of heat recovery can reach 52.9% in this model.
- Copyright
- © 2015, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Bing Xia AU - Yebin Yin AU - Jinghong Lian AU - Guang Yang AU - Guoyou Xu AU - Xiang Gou AU - Enyu Wang AU - Liansheng Liu AU - Jinxiang Wu PY - 2015/11 DA - 2015/11 TI - Numerical Simulation on Heat Pipe Heat Exchanger: Effects of Different Wind Speeds BT - Proceedings of the 2015 4th International Conference on Computer, Mechatronics, Control and Electronic Engineering PB - Atlantis Press SP - 270 EP - 274 SN - 2352-5401 UR - https://doi.org/10.2991/iccmcee-15.2015.51 DO - 10.2991/iccmcee-15.2015.51 ID - Xia2015/11 ER -