Study on the Hourly Performance of A Solar Driven Ejector Refrigerant System
- DOI
- 10.2991/iccasm.2012.119How to use a DOI?
- Keywords
- Solar ejector refrigeration,Hourly performance, Solar radiation
- Abstract
An experimental setup about solar ejector refrigeration is designed and built using HFC134a as working fluid in this paper. Based on Zhengzhou meteorological parameters, the hourly coefficient of performance(COP), energy efficient ratio(EER), cooling capacity and other parameter about the ejector refrigeration system have been researched with the solar radiation changed, The experimental data show that the hourly COP and EER of the system change constantly, and it has been influenced by the solar radiation, the ambient temperature, generator temperature, and condenser temperature et al., and the cooling capacity, heat transfer capacity about the exchanger, and generator temperature appear rise and fall in the research range. The average daily COP is 0.18 at the July 26, the average EER can up to 3.5.
- Copyright
- © 2012, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Huifan Zheng AU - Xiaowei Fan AU - Lihe Zhang PY - 2012/08 DA - 2012/08 TI - Study on the Hourly Performance of A Solar Driven Ejector Refrigerant System BT - Proceedings of the 2012 International Conference on Computer Application and System Modeling (ICCASM 2012) PB - Atlantis Press SP - 470 EP - 472 SN - 1951-6851 UR - https://doi.org/10.2991/iccasm.2012.119 DO - 10.2991/iccasm.2012.119 ID - Zheng2012/08 ER -