PD Detection on Power Cable with Peak-Correlation Method
- DOI
- 10.2991/ecae-17.2018.6How to use a DOI?
- Keywords
- component; oscillating voltage; cable; partial discharge; peak-correlation; location
- Abstract
Oscillating voltage is an effective method for PD detection in XLPE cable. In this paper, it mainly described the principle of oscillating waveform test system (OWTS) for PD detection and proposed the peak-correlation method for the location of partial discharge points. Then, an oscillating waveform test system for 10kV cable was established in the laboratory. It was used for the PD testing of a 500 meters long cable. In the end of the paper, the waveform characteristics of the direct pulse and reflect pulse were analyzed. With this feature, the problem caused by multi PDs in a single time window could be effectively solved which greatly improved the reliability and automation of the PD location algorithm. Experimental results show that oscillating voltage can effectively excite the generation of partial discharge and peak-correlation is a valid method for PD location with sufficient accuracy and reliability.
- Copyright
- © 2018, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Lihui Zhang AU - Yanda Li AU - Mingjia Zhang AU - Hechen Liu AU - Yunpeng Liu PY - 2017/12 DA - 2017/12 TI - PD Detection on Power Cable with Peak-Correlation Method BT - Proceedings of the 2017 2nd International Conference on Electrical, Control and Automation Engineering (ECAE 2017) PB - Atlantis Press SP - 27 EP - 30 SN - 2352-5401 UR - https://doi.org/10.2991/ecae-17.2018.6 DO - 10.2991/ecae-17.2018.6 ID - Zhang2017/12 ER -