An Adaptive Current Quick Break Protection Based on Power Frequency Variation
- DOI
- 10.2991/ammee-17.2017.162How to use a DOI?
- Keywords
- R-SFCL, distance protection, power frequency variation distance relay.
- Abstract
A mathematical model of resistance type superconducting fault current limiter (R-SFCL) is established and the influence to power frequency variation distance relay has been analyzed firstly. Then, it indicates that the input of the superconducting current limiter changes the circuit model before and after the fault, so that the power frequency variation impedance relay based on the pre fault memory data does not satisfy the superposition condition. An adaptive current quick break protection considering the impedance characteristics of superconducting current limiter is proposed, after the similarity and difference in principle and performance of the adaptive current quick break protection and power frequency variation impedance relay are discussed. Finally, the feasibility and effectiveness of the new method is verified by simulation in EMTDC/PSCAD.
- Copyright
- © 2017, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Hui Li AU - Zixuan Wang AU - Xiangning Lin AU - Ning Xu AU - Zhengtian Li AU - Fanrong Wei AU - Siyi Liu AU - Jinguang Huang PY - 2017/06 DA - 2017/06 TI - An Adaptive Current Quick Break Protection Based on Power Frequency Variation BT - Proceedings of the Advances in Materials, Machinery, Electrical Engineering (AMMEE 2017) PB - Atlantis Press SP - 845 EP - 852 SN - 2352-5401 UR - https://doi.org/10.2991/ammee-17.2017.162 DO - 10.2991/ammee-17.2017.162 ID - Li2017/06 ER -